Dry transformers with epoxy insulation and power rating 100 – 2500 kVA
Brief description of dry transformers with epoxy insulation
Dry transformers are fire resistant and highly stable when short circuits. They are easy in use and environmental friendly. Indicators of resistance when overheating – F (155 C). Grade of resistance IP – 00 (without safety covering) IP – 21 and IP – 23 C (with covering). Low voltage winding is made from aluminum or copper foil, high voltage winding – from aluminum or copper cable. Draw shows how to connect tensions, the scheme and the group of connections, arranging introductions HV (High Voltage) and LV (Low Voltage) as well as type of introductions (metal track or cable) depending on client’s request. Package is supplied with temperature sensor and transmitter which first gives warning signal, next gives second signal and turns off transformer after overheating winding and insulation according to norm (145 C – warning signal, 165 C - second signal and shut down).

Table contains information about size, weight of dry transformers with safety covering power rating 100-2500 kVA
Power, kVA |
Loss, Vt |
Weight, kg |
Size, mm |
Ro |
Rk. at 75”C |
à |
b |
ñ |
d |
å |
f |
100 |
320 |
1700 |
990 |
1210 |
810 |
1490 |
520 |
125 |
40 |
160 |
520 |
2000 |
1350 |
1450 |
810 |
1520 |
520 |
125 |
40 |
250 |
880 |
3100 |
1470 |
1450 |
810 |
1650 |
520 |
125 |
40 |
400 |
1100 |
5000 |
1800 |
1600 |
920 |
1710 |
670 |
125 |
40 |
630 |
1450 |
6600 |
2170 |
1700 |
920 |
1860 |
670 |
125 |
40 |
1000 |
2000 |
8800 |
3160 |
1840 |
980 |
2100 |
820 |
160 |
50 |
1600 |
2800 |
13000 |
4260 |
2050 |
1300 |
2280 |
820 |
160 |
50 |
2500 |
6800 |
19000 |
6900 |
2320 |
1300 |
2650 |
1070 |
200 |
70 |
Attention: arranging HV introductions and LV as well as the type of introductions (track or cable) for demanding the custome
|
Download video
Presentation of Ltd "Transformator service"
- Contact: Prospekt Mira 101-B, 29000,
- Khmelnitsky, Ukraine ( see on a map )

- Oil-immersed transformers from 25 kVA till 1000 kVA
- Dry-type transformers from 100 kVA till 2500 kVÀ


22.09.2008 „Transformator service” has applied quality standard ISO 9001.
21.11.2007 Since October 2007 "Transformator service" has started to implement ISO 9001.
01.12.2005 Ukrainian certificate for oil-immersed transformers with power rating 250 - 400 kVÀ
01.10.2005 Russian certificate for oil-immersed transformers with power rating 25 - 160 kVÀ


Which production are you interested in ?
|